Full scale value can be programmed (teaching possible)
Sensor: analog Hall sensor
Nominal width: DN 32 / 40 / 50
Process connection: female thread G 1 1/4..G 2 (further process connections available on request)
Metering range: 50....300 l/min for details see table "Ranges"
Pressure loss: ~ 1 bar at Qmax
Qmax.: up to 300 l/min
Measurement accuracy: 8% of full scale value
Pressure resistance: PS 200 bar
Medium temperature: -20..+85 °C, optionally -20..+120 °C
Ambient temperature: -20..+70 °C
Media: water
Wiring: see section "Wiring"
Materials medium-contact
Brass construction: CW614N nickelled, CW614N, 1.4305, 1.4310, hard ferrite,
Stainless steel construction: 1.4571, 1.4310, hard ferrite
Materials, non medium-contact: CW614N nickelled
Supply voltage: 18..30 V DC
Power consumption: < 1 W
Output: Current output 4..20 mA (alternatively 0..20 mA)
Max. load 500 Ohm
Display: yellow LED (On = Normal / Off = Alarm / rapid flashing = Programming
Electrical connection: for round plug connector M12x1, 4-pole
Ingress protection: IP 67
Weight: see table "Dimensions and weights"
Conformity: CE
Installation location