Metrel MI 3155 Standard set Multifunctional Electrical Installation Tester (50 V ~ 2500 V)
Continuity
Test Current 7 mA 2-wire:
0.00 Ω ... 19.99 Ω / 0.1 Ω / ±(5 % of r. + 3 digits)
20.0 Ω ... 1999 Ω / 1 Ω / ±(5 % of r. + 3 digits)
Test Current 200 mA 2-wire:
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(3 % of r. + 3 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of r.)
200.0 Ω ... 1999 Ω / 1 Ω / ±(5 % of r.)
Test Current 200 mA 4-wire:
0.000 Ω ... 0.049 Ω / 0.001 Ω / ±(30 digits)
0.050 Ω ... 19.999 Ω / 0.001 Ω / ±(3 % of r. + 10 digits)
20.00 Ω ... 199.99 Ω / 0.01 Ω / ±(5 % of r.)
200.0 Ω ... 1999.9 Ω / 0.1 Ω / ±(5 % of r.)
Insulation Resistance
Test Voltage 50/100/250 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of r. + 3 digits)
20.0 MΩ ... 99.9 MΩ / 0.1 MΩ / ±(10 % of r.)
100.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(20 % of r.)
Test Voltage 500/1000 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of r. + 3 digits)
20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of r.)
200 MΩ ... 999 MΩ / 1 MΩ / ±(10 % of r.)
Test Voltage 2500 V:
0.00 MΩ ... 19.99 MΩ / 0.01 MΩ / ±(5 % of r. + 3 digits)
20.0 MΩ ... 199.9 MΩ / 0.1 MΩ / ±(5 % of r.)
200 MΩ ... 999 MΩ / 1 MΩ / ±(10 % of r.)
1.00 GΩ ... 19.99 GΩ / 0.01 GΩ / ±(10 % of r.)
RCD Test
RCD Uc (Contact Voltage):
0.00 V ... 19.99 V / 0.1 V / (-0 %/+15 %) of r. ± 10 digits
20.0 V ... 99.9 V / 0.1 V / (-0 %/+15 %) of r.
RCD (t) (Trip Time):
0.00 ms ... 40.0 ms / 0.1 ms / ±1 ms
0.0 ms ... max. time / 0.1 ms / ±3 ms
RCD I Ramp (Trip Current):
0.2×IΔN ... 2.2×IΔN / 0.05×IΔN / ±0.1×IΔN
Impedance
Zline (L-L, L-N) & Zloop (L-PE):
0.00 Ω ... 9.99 Ω / 0.01 Ω / ±(3 % of r. + 3 digits)
10.0 Ω ... 99.9 Ω / 0.1 Ω / ±(5 % of r.)
100 Ω ... 999 Ω / 1 Ω / ±(10 % of r.)
1.00 kΩ ... 9.99 kΩ / 10 Ω / ±(10 % of r.)
Voltage & Frequency
Voltage TRMS (0, 14 ... 500 Hz):
0 V … 550 V / 1 V / ±(2 % of r. + 2 digits)
Frequency:
0.00 Hz ... 499.9 Hz / 0.01 Hz / ±(0.2 % of r. + 1 digit)
Earth Resistance
3-wire Method:
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(5 % of r. + 5 digits)
20.0 Ω ... 199.9 Ω / 0.1 Ω / ±(5 % of r. + 5 digits)
200.0 Ω ... 9999 Ω / 1 Ω / ±(5 % of r. + 5 digits)
2-clamp Method:
0.00 Ω ... 19.99 Ω / 0.01 Ω / ±(10 % of r. + 10 digits)
20.0 Ω ... 39.9 Ω / 0.1 Ω / ±(20% - 30 % of r.)
General Data
Power Supply: 7.2 V (4400 mAh Li-Ion battery pack)
Overvoltage Category: 600 V CAT III; 300 V CAT IV
Protection Class: Double insulation
COM Port: BT, USB, RS232
Display: 4.3 inch Colour TFT touch screen (480 x 272 pixels)
Dimensions (L x H x W): 252 x 111 x 165 mm
Weight: 1.78 kg
Standard set
Instrument MI 3155 EurotestXD
4400 mAh battery pack
Power supply adapter 12 V / 3 A
Plug commander, 1.5 m
Test lead, 4-wire, 1.5 m
Test lead, 3-wire, 1.5 m
Test lead, 2-wire, 2.5 kV, 1.5 m
Test probe, 4 pcs (black, blue, green, red)
Crocodile clip, 6 pcs (black – 2 pcs, blue – 1 piece, green – 1 piece, red – 2 pcs)
Earth set 20 m
USB cable
Soft carrying bag
Soft carrying neck belt
Calibration certificate
Short instruction manual
Instruction manual*
Metrel ES Manager BASIC Licence*
SW 1201 Metrel ES Manager (program installation)*
*SW 1201 Metrel ES Manager and all documentation can be downloaded free of charge from Metrel Web server or Metrel Documentation center
Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.
By subscribing, you agree to our Terms of Service and Privacy Policy.
Direct access to our certified experts