MEGGER MS-2A Circuit Breaker and Overcurrent Relay Test Set
Ammeter
Operating Modes (switch-selected)
Memory
Normal
Display: 31/2 digit, extra-bright LED display with 0.3 in. (7.62mm) numerals
Ranges (switch-selected): 0 to 1.999/19.99/199.9/750 A
Continuous Accuracy (overall ammeter system)
±1% of reading, ±1 digit on three high ranges
±1% of range, ±1 digit on low range
Timer
Display: 5-digit, extra-bright, LED display with 0.3 in. (7.62mm) numerals
Ranges (switch-selected)
0 to 99.999 s
0 to 999.99 s
0 to 99999 cycles
Accuracy: ±0.005% of reading, ±1 digit
Timer Control Circuit: This circuit automatically starts the timer when the output is energized
and automatically stops the timer and de-energizes the output when
the device under test operates. This circuit accommodates the following
test conditions by simple switch selection of the appropriate mode:
Current Actuated: Used to test a device that has no auxiliary contacts
to monitor, such as a single-pole circuit breaker. The timer stops when
the output current is interrupted.
Normally Closed: Used to test a device with normally closed contacts.
The timer stops and the output is de-energized when the contacts open.
Normally Open: Used to test a device with normally open contacts. The
timer stops and the output is de-energized when the contacts close.
Enclosure: The test set is housed in a high strength, molded, suitcase-type
enclosure with carrying handle and removable cover. Storage space is
provided for test leads.
Dimensions: 18 W X 9.5H X 13.5 D in. (457.2 W x 241.3 H x 342.9 mm)
Weight: 33 lb (15 kg)