Power supply AC 220V/110V, 50/60Hz;
Cell type:
1) Standard: 1.2V1, 2V, 6V and 12V
2) Customized: 12V ONLY or other uncommon battery types.
Discharge voltage range:
10V-13.8V (nominal: 12V): 0-100A
10V-27.6V (nominal: 24V): 0-200A
10V-41.4V (nominal: 36V): 0-200A
10V-55.2V (nominal: 48V): 0-200A
10V-92V (nominal: 80V): 0-200A
Discharge current range:
Single load bank: 10A-200A
Parallel load: 10A-400A
Accuracy:
Current: 1%
Voltage: 0.5% – 0.8%
Resolution:
Current: 0.1 A or 0.5%
Voltage: 0.001 V
Sampling Interval: 5s - 1min
Discharge pattern: Constant current
Display: 128*64 pixel LCD
Data transfer: USB, Radio Frequency (for DAC to load bank)
Operation Temperature: 0℃~40℃ (32 – 104 °F)
Humidity: 5%~90% Relative humidity
Standard: CE marking, EMC standard
Main Unit Dimension: 74*40*73cm
Main unit Weight: 55 kg