Weight: 9.5 oz
Software: Free, USB Based. Resident on Meter, Nothing to Download.
Impedance: >100 kΩ
Compliance: CE, cUL, RoHS 2, UL
Input Type: Thermocouple, RTD
Switch Type: N/A
Display Note: Dual-line, 6-digit display. Resolution: 1° (up to four digits) or 0.1° (up to five digits)
RTD Accuracy: 10 Ω Copper, 120 Ω Nickel: ± 0.1 °C; 100 Ω Platinum, 1000 Ω Platinum: ± 0.4 °C
Output Signal: Current
Supply Voltage: 85 to 265 Vac
RTD Input Range: 10 Ω Copper: -328 to 500 °F, 100 Ω Platinum: -328 to 1562 °F,120 Ω Nickel: -110 to 500 °F, 1000 Ω Platinum: -328 to 900 °F
Number of Digits: 6
Electrical Output: 4 to 20 mA
Enclosure Ratings: IP65, NEMA Type 4X
Power Consumption: 20 W max
Relative Humidity: 0 to 90%, Non-Condensing
Supply Power Type: AC
Display Resolution: Upto 4 Digits: 1°; Upto 5 Digits: 0.1°
Thermocouple Accuracy: Type J, K, T, E: ± 1°C; Type R, S, B, N, C: ± 2°C
Temperature Sensor Type: RTD or Thermocouple
Storage Temperature, Max: 185 °F
Storage Temperature, Min: -40 °F
Thermocouple Input Range: Type J: -200 to 2000 °F, Type K: -200 to 2400 °F, Type T: -200 to 752 °F, Type E: -200 to 1800 °F, Type R: -50 to 3000 °F, Type S: -50 to 3000 °F, Type B: 752 to 3300 °F, Type N: -100 to 2300 °F, Type C: 32 to 4100 °F
Operating Temperature, Max: 149 °F
Operating Temperature, Min: -4 °F